首页> 外文会议>European corrosion congress >Electrochemical monitoring of damaged thermally sprayed aluminium coatings on steel in a simulated marine immersion environment at different temperatures
【24h】

Electrochemical monitoring of damaged thermally sprayed aluminium coatings on steel in a simulated marine immersion environment at different temperatures

机译:在模拟海洋浸泡环境中,在不同温度下对钢上受损的热喷涂铝涂层进行电化学监测

获取原文

摘要

In this paper the corrosion behaviour of damaged thermally sprayed coatings is presented. Commercially pure Al was arc-sprayed onto carbon steel substrates and exposed to synthetic seawater at two different temperatures (5°C and boiling seawater (~101.5°C)) for 5000h. Prior to exposure circular defects were generated in the coating to expose 4-5% area of the substrate. The samples were left at their free corrosion potential (vs saturated calomel electrode (SCE)) and the corrosion rate was monitored using linear polarisation resistance (LPR) technique for 2000h. Once the tests were completed the samples were sectioned and microstructural characterisation was carried out. The potential of the TSA-coated steel with a 4-5% holiday was found to decrease initially and then reach a higher value with time at both temperatures. At 5°C, the potential decreased from -820 mV (SCE) at the start to -1080 mV (SCE) after ~300h, reaching -970 mV (SCE) after 1200h. The minimum (-1200mV SCE) was reached earlier (~16h) in boiling seawater, finally reaching values between -800mV (SCE) and -840mV (SCE) after 640h. Microstructural examination revealed a thin layer of calcareous deposit on the exposed steel surface. This calcareous deposit had two-layer structure with Mg(OH)_2 close to the substrate and CaCC>3 away from it at 5°C, and comprised of Mg(OH)_2 only in boiling seawater. The layer formed in situ seems to have provided a barrier and protected the steel from further corrosion giving low corrosion rates of 4-5um/y at 5°C and 6-15um/y in boiling seawater after 2000h. Thus, Al coating is able to protect steel substrates at extreme temperatures even when defects are present.
机译:本文介绍了损坏的热喷涂涂层的腐蚀行为。将商业纯铝电弧喷涂到碳钢基底上,并在两种不同温度(5°C和沸腾海水(〜101.5°C))下暴露于合成海水中5000h。在暴露之前,在涂层中产生圆形缺陷以暴露4-5%面积的基材。使样品保持其自由腐蚀电位(相对于饱和甘汞电极(SCE)),并使用线性极化电阻(LPR)技术监测腐蚀速率2000h。测试完成后,将样品切片并进行微结构表征。发现在两个温度下,具有4-5%空隙的TSA涂层钢的电势先下降,然后随时间达到更高的值。在5°C下,电势从开始时的-820 mV(SCE)降低到〜300h之后的-1080 mV(SCE),在1200h之后达到-970 mV(SCE)。在沸腾的海水中更早(〜16h)达到最小值(-1200mV SCE),在640h之后最终达到-800mV(SCE)和-840mV(SCE)之间的值。显微组织检查表明,在裸露的钢表面上有一层钙质沉积物。该钙质沉积物具有两层结构,其中Mg(OH)_2靠近底物,CaCC> 3在5°C时离它很近,并且仅在沸腾的海水中由Mg(OH)_2组成。原位形成的层似乎提供了屏障,并保护了钢免于进一步腐蚀,从而在5°C下的腐蚀速率低至4-5um / y,在沸腾的海水中2000h后腐蚀速率低至6-15um / y。因此,即使存在缺陷,Al涂层也能在极端温度下保护钢基材。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号