摘要

The survey of magnetic field measurements from the 154/31.5 kV substation in the city of Antalya have been proposed for an occupational exposure assessment. The magnetic field measurements are carried out from a substation equipment; including all transformers, circuit breakers, feeders and buses, under the in-coming and out-going power lines and operator tables surrounding the substation. The magnetic field is measured as 0.46 μT at the minimum loaded season and 1.34 μT at maximum loaded season over the operator desk. Workers are exposed to 0.3 μT and even more magnetic field for eight hours period per day. In switchgear regions, the maximum magnetic field measurement is 20 μT at the minimum loaded season and may reach up to 65 μT. Outdoor magnetic field values at the circuit breaker region may approach to 45 μT depending on operator heights.
机译:已提议对安塔利亚市154 / 31.5 kV变电站的磁场测量进行调查,以进行职业暴露评估。磁场测量是通过变电站设备进行的;包括变电站进出的电力线和操作员桌下面的所有变压器,断路器,馈线和母线。在操作台上,磁场在最小负载季节的测量值为0.46μT,在最大负载季节的测量值为1.34μT。工人每天要暴露0.3μT甚至更多的磁场,持续八个小时。在开关柜区域,在最小负载季节,最大磁场测量值为20μT,最高可能达到65μT。根据操作员的身高,断路器区域的室外磁场值可能接近45μT。