首页> 外文会议>International Conference on Electrical, Computer and Communication Technologies >Condition evaluation of stator winding insulation of vintage high voltage turbine generator
【24h】

Condition evaluation of stator winding insulation of vintage high voltage turbine generator

机译:老式高压水轮发电机定子绕组绝缘状态评估

获取原文

摘要

Degradation of dielectric insulation system happens in turbine generators in service. T hermal, electrical, ambient and mechanical forces attack the potential barrier of power windings and reduce the electrical strength. Sudden failure and forced outage can be averted by condition assessment of generator insulation. This paper presents state-of-art diagnosis tools to evaluate the dielectric insulation properties of stator winding of generators. Degradation mechanism in insulation is dealt with physical model and electrical equivalent circuit. Test results of 25 MW, 11 KV TG of four decades old are analyzed to evaluate the insulation properties. Correlation is made between tan δ, partial discharge, corona probe data with visual examination. Corrective actions are listed to improve the insulation performance. Utility is advised to monitor the machine parameters on load and repeat dielectric tests to avoid forced outages due to insulation failure. It is suggested to plan rewinding with state of art of insulation technology to enhance the life of machine.
机译:使用中的涡轮发电机会发生介电绝缘系统的退化。温度,电气,环境和机械力会侵蚀电源绕组的势垒并降低电气强度。发电机绝缘状况评估可以避免突然的故障和强迫停机。本文介绍了最新的诊断工具,用于评估发电机定子绕组的介电绝缘性能。绝缘的退化机理是通过物理模型和等效电路来解决的。分析了四十年之久的25 MW,11 KV TG的测试结果,以评估绝缘性能。肉眼观察到tanδ,局部放电,电晕探针数据之间的相关性。列出了纠正措施,以改善绝缘性能。建议公用事业公司在负载下监视机器参数并重复进行介电测试,以免由于绝缘故障而导致强制中断。建议使用最新的绝缘技术计划收卷,以延长机器的使用寿命。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号