首页> 外文会议>Annual Pulp and Paper Industry Technical Conference >One mill's experience using MAC testing to evaluate vacuum interrupter integrity in 15KV vacuum circuit breakers
【24h】

One mill's experience using MAC testing to evaluate vacuum interrupter integrity in 15KV vacuum circuit breakers

机译:一厂使用MAC测试评估15KV真空断路器中真空灭弧室完整性的经验

获取原文
获取外文期刊封面目录资料

摘要

For most of the first 100 years of existence of electrical power distribution systems, circuit breakers used either air- or oil-media interrupters. In the 1970's, the application of vacuum interrupter (VI) circuit breakers changed that but also left a void for how to predict remaining service life of the necessarily sealed VI. This paper reports the results of use of alternate testing technology employing a magnetron device to apply a magnetic field, external to the VI, to enable estimation of vacuum integrity. Results are reported from one mill outage, encompassing approximately 50 VI's, which were also subjected to the mill's regular regimen of PM testing for vacuum circuit breakers. The data collected is presented along with suggestions for integration of the MAC testing technology into existing circuit breaker PM efforts.
机译:在配电系统存在的前100年中的大多数时间里,断路器都使用空气或石油介质断路器。在1970年代,真空灭弧室(VI)断路器的应用发生了变化,但也为如何预测必须密封的VI的剩余使用寿命留下了空白。本文报告了使用替代测试技术的结果,该技术采用磁控管设备在VI外部施加磁场,以估计真空完整性。报告的结果来自一个工厂的停运,涉及大约50个VI,这些结果也受到该工厂针对真空断路器的PM测试的常规处理。提出了收集的数据以及将MAC测试技术集成到现有断路器PM工作中的建议。