首页> 外文会议>China International conference on electricity distribution >Research for the fast distance protection of transmission lines based on equal transfer processes
【24h】

Research for the fast distance protection of transmission lines based on equal transfer processes

机译:基于等转移过程的传输线快速保护研究

获取原文

摘要

Taking into account the error caused by differential, two factors' impact on the d i stance protection algorithm after equal transfer processes are studied, including the sampling rate and cut-off frequency of the low-pass filter. It comes to a conclusion that increasing the sampling rate can reduce the error caused by differential and cutting down the cut-off frequency can reduce the variance of the least square method, which is verified by the ATP simulation and dynamic physical simulation results. Combined with the simulation results, the impact caused by the length of data window is studied by analyzing the performances of the proposed algorithm. By optimizing the sampling rate, the cutoff frequency, and the length of data window, the distance measuring error can be achieved within 5% at approximately 10ms after the fault occurrence.
机译:考虑到差异引起的误差,研究了对等转移过程后对D i姿势保护算法的两个因素的影响,包括低通滤波器的采样率和截止频率。得出结论,增加采样率可以减少由差分和切割截止频率引起的误差可以降低最小二乘法的方差,由ATP仿真和动态物理仿真结果验证。结合仿真结果,通过分析所提出的算法的性能来研究由数据窗口长度引起的影响。通过优化采样率,截止频率和数据窗口的长度,在故障发生后,距离测量误差可以在大约10ms的5%内实现。