Influence on the unbalance of three-phase voltage of bus brought by multi-tap arc suppression coil system

机译:多踢弧抑制线圈系统带来总线三相电压不平衡的影响

获取原文

摘要

However, in practical use, the unbalance of the three-phase voltage of the 10 (20) kV bus is too large due to the unreasonable gear of the grounding transformer and unreasonable design of damp resistance. Alarming signal is even mistakenly sent. In the grid system with insulated neutral points, the neutral-point-to-ground offset voltage is generated due to the unequal phase-to-ground capacitance (caused by the arrangement of the lines). IN this paper we think that adjusting the tap changer of the grounding transformer can decrease the offset voltage caused by the incomplete conductor transposition. The validity of this method is proved through real cases.
机译:然而,在实际使用中,由于接地变压器的不合理齿轮和潮湿的潮湿设计不合理地设计,10(20)kV总线的三相电压的不平衡太大。甚至错误地发送了警报信号。在具有绝缘中性点的网格系统中,由于不相等的相对地电容(由线的布置引起)产生中性点对地偏移电压。在本文中,我们认为调整接地变压器的抽头变换器可以降低由不完全导体转换引起的偏移电压。通过实际案例证明了这种方法的有效性。