首页> 外文会议>China International conference on electricity distribution >Influence on the unbalance of three-phase voltage of bus brought by multi-tap arc suppression coil system
【24h】

Influence on the unbalance of three-phase voltage of bus brought by multi-tap arc suppression coil system

机译:多抽头消弧线圈系统对母线三相电压不平衡的影响

获取原文

摘要

However, in practical use, the unbalance of the three-phase voltage of the 10 (20) kV bus is too large due to the unreasonable gear of the grounding transformer and unreasonable design of damp resistance. Alarming signal is even mistakenly sent. In the grid system with insulated neutral points, the neutral-point-to-ground offset voltage is generated due to the unequal phase-to-ground capacitance (caused by the arrangement of the lines). IN this paper we think that adjusting the tap changer of the grounding transformer can decrease the offset voltage caused by the incomplete conductor transposition. The validity of this method is proved through real cases.
机译:然而,在实际使用中,由于接地变压器的齿轮不合理和阻尼电阻的设计不合理,10(20)kV母线的三相电压的不平衡太大。警报信号甚至被错误地发送。在具有绝缘中性点的电网系统中,由于不相等的相对地电容(由线路布置引起),会产生中性点对地偏移电压。在本文中,我们认为调整接地变压器的抽头变换器可以减少由于导体换位不完全而引起的偏移电压。通过实际案例证明了该方法的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号