首页> 外文会议>China International conference on electricity distribution >Research on non-fault-phase current characteristics in grounding fault in power transmission grid
【24h】

Research on non-fault-phase current characteristics in grounding fault in power transmission grid

机译:输电网接地故障中无故障相电流特性的研究

获取原文
获取外文期刊封面目录资料

摘要

When grounding fault occurs in power transmission line in neutral-point grounded system, fault current of the fault phase tends to increase dramatically. In the meantime, the amplitude and phase of the current of non-fault phase also changes abruptly in some degree due to mutual inductance between phases. Firstly, by building model with complete electrical parameters based on induction between phases, this paper illustrates current characteristics of non-fault phase when single-phase grounding occurs in system with neutral-point solid grounding using physical conception. Then, RTDS model is built incorporating parameters of actual system to verify the accuracy and validity of the analysis model with complete electrical parameters using real-time simulation. In conclusion, amplitude and phase of non-fault phase is influenced by load condition, position of fault, system impedance, line impedance, etc., which offer favorable references for judging grid fault characteristics and positioning of fault in a fast and effective way.
机译:在中性点接地系统的输电线路中发生接地故障时,故障相的故障电流趋于急剧增加。同时,由于相之间的互感,非故障相电流的幅度和相位也会在某种程度上突然改变。首先,通过基于相间感应建立具有完整电参数的模型,利用物理概念,阐述了在具有中性点固体接地的系统中发生单相接地时的无故障相的电流特性。然后,建立包含实际系统参数的RTDS模型,以通过实时仿真验证具有完整电气参数的分析模型的准确性和有效性。综上所述,非故障相的幅值和相位受负载条件,故障位置,系统阻抗,线路阻抗等的影响,为快速有效地判断电网故障特性和故障位置提供了有益的参考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号