首页> 外文会议>China International conference on electricity distribution >Analysis on voltage deviation inactive distribution network and active voltage management
【24h】

Analysis on voltage deviation inactive distribution network and active voltage management

机译:电压偏差无源配电网分析及有源电压管理

获取原文

摘要

Large scale of distributed generation (DG) in distribution network results in potential power quality problems, such as voltage deviation, fluctuation and flick, or harmonics. This paper starts from analysis of voltage deviation for DGs. System short circuit capacity, R/X ratio, DG capacity and power factor are investigated to have main impacts on voltage deviation level. A case study model is developed using DigSilent. Penetration ratio (PR), distribution (DT) and dispersion (DP) level are defined to describe DG connection status. Simulation is conducted to explore the voltage deviation rules in distribution network with high penetration level of DGs. The maximum capacity for distribution network to accommodate DG is estimated under limitation of voltage deviation level by power quality standard. According to active distribution network principles, some guidelines for active voltage management are presented.
机译:配电网络中的大规模分布式发电(DG)会导致潜在的电能质量问题,例如电压偏差,波动和波动或谐波。本文从分析DG的电压偏差开始。研究了系统的短路容量,R / X比,DG容量和功率因数,它们对电压偏差水平有主要影响。使用DigSilent开发了一个案例研究模型。定义了渗透率(PR),分布(DT)和分散(DP)级别来描述DG连接状态。进行了仿真,以探索具有高渗透率的DGs的配电网中的电压偏差规则。配电网容纳DG的最大容量是根据电能质量标准在电压偏差水平的限制下估算的。根据有源配电​​网原理,提出了一些有源电压管理指南。