摘要

When the impedance criterion is used to analyze the stability of the three-phase inverter-grid system, the impedance acquisition of the grid-connected inverter is particularly important. In the stationary reference frame, the equivalent admittance accurately characterizes the impedance characteristics of the inverter. But it varies with the grid impedance and contains the frequency coupling component. This makes it difficult to measure the admittance accurately by the off-the-shelf frequency response analyzer (FRA). In this paper, a method is proposed to estimate the inverter impedance, which takes into account the influence of grid impedance and the frequency coupling effect. Consequently, correct stability analysis of the grid-inverter system is guaranteed. Simulation and experimental results are presented to demonstrate the effectiveness of the proposed method.
机译:当使用阻抗标准来分析三相逆变器 - 电网系统的稳定性时,网格连接逆变器的阻抗采集尤为重要。在静止参考框架中,等效导纳精确表征逆变器的阻抗特性。但它随网格阻抗而变化并包含频率耦合元件。这使得难以通过现成的频率响应分析仪(FRA)准确测量终止。本文提出了一种方法来估计逆变器阻抗,这考虑了电网阻抗和频率耦合效应的影响。因此,保证了网格逆变器系统的正确稳定性分析。提出了模拟和实验结果,以证明所提出的方法的有效性。