Rotor temperatures of field windings are seldom measured, as permanent installation of sensors on the rotor is often difficult and can present undesired risks. However, new possibilities exist with the use of fiber Bragg gratings (FBGs). Up to 20 sensors can be mounted in series in a single fiber. Moreover, several fibers can be used in parallel, and the signal passed from the rotor to the stator through a multichannel optical rotating joint. A demonstration of such a use of FBGs has been undertaken in a Hydro-Quebec power plant, where 32 pole-to-pole connections and 28 poles were instrumented. Measurements were carried out during a heat run test and FBG results are compared with average temperature calculated from voltage and current.
机译:现场绕组的转子温度很少测量,因为转子上的传感器永久安装通常困难,并且可以提出不希望的风险。但是,使用光纤布拉格光栅(FBG)存在新的可能性。最多20个传感器可以在单根光纤中串联安装。此外,若干纤维可以并联使用,并且信号通过多通道光学旋转接头从转子从转子传递到定子。在水电 - 魁北克电厂进行了这种使用FBG的示范,其中32个杆极连接和28个杆仪表。在热运行测试期间进行测量,并将FBG结果与电压和电流计算的平均温度进行比较。