首页> 外文会议>IEEE electrical insulation conference >Thermal ageing effect on the failure time of oil-paper insulation at combined AC-DC voltage
【24h】

Thermal ageing effect on the failure time of oil-paper insulation at combined AC-DC voltage

机译:AC-DC电压下油纸绝缘失效时间的热老化效应

获取原文

摘要

The oil-paper insulation of converter transformer withstands a long time electrical aging by combined AC-DC voltage and thermal aging during operation. The aging failure mode of converter transformers insulation exhibits a great difference with that of AC transformers. In this paper, a set of accelerated thermal aging experiments at 130 °C were designed, oil-paper specimens were aged for 5, 10, 20 and 35 days, respectively. The unaged oil-paper specimens were also prepared for comparison. The breakdown voltage and failure time of oilpaper specimens of different aging times at AC and combined AC-DC voltage were measured, respectively. The relationship between the failure time and aging time is obtained by using Weibull analysis method. The experiment results show that the breakdown voltage of oil-paper specimens all decrease not much with the increase of thermal aging time. The oil-paper specimens have a longer failure time at combined AC-DC voltage compared with that at AC voltage.
机译:转换器变压器的油纸绝缘通过组合的AC-DC电压和操作期间热老化承受了长时间的电老化。转换器变压器绝缘的老化失效模式与AC变压器的差异很大。本文设计了一组加速热老化实验,设计了130℃,分别为5,10,20至35天的油纸试样。还制备了一个单位的油纸标本进行比较。分别测量AC和组合AC-DC电压不同老化时间的脱粒电压和擦除纸纸张的故障时间。通过使用威布尔分析方法获得故障时间和老化时间之间的关系。实验结果表明,随着热老化时间的增加,油纸试样的击穿电压并不多大。与AC电压相比,油纸样品在组合的AC-DC电压下具有较长的故障时间。