Influence of angles of V-strings on DC flashover characteristics of polluted insulators in high altitude areas

机译:V串角对高海拔地区污染绝缘子直流闪络特性的影响

获取原文

摘要

Using a high-speed camera, the fundamental behaviors of arcs on the surfaces of two types of 300kN porcelain insulators were studied under dc voltages. The test results showed that it was quite easy for the arcs on porcelain insulator surfaces to levitate from insulator surfaces in high altitude areas (1970m). The influence of angles, used for different V-strings of insulator configurations, on DC flashover behaviors of contaminated insulators was very obvious. In this paper, the effects of the angles of V-strings on DC flashover characteristics of two types polluted insulators (anti-fog insulator and tri-shed DC suspension insulator) were investigated.
机译:使用高速摄像头,在直流电压下研究了两种类型300kn瓷绝缘子的表面上的电弧的基本行为。测试结果表明,瓷绝缘子表面上的弧度非常容易,以从高海拔地区(1970米)中的绝缘体表面浮出。用于不同V型绝缘体配置的角度的影响,在污染绝缘体的直流闪络行为上非常明显。在本文中,研究了V型角度对两种污染绝缘体(防雾绝缘体和三棚DC悬架绝缘子)的直流闪络特性的影响。