首页> 外文会议>IEEE Region 10 Conference >Research on Preventing Zone 3 Distance Relays From Operating Incorrectly Caused by Non-fault Overload
【24h】

Research on Preventing Zone 3 Distance Relays From Operating Incorrectly Caused by Non-fault Overload

机译:防止区域3距离中继从非故障过载导致的距离中继的研究

获取原文

摘要

Transmission lines are operating close to their limit with the promotion of power networks interconnection. The possible non-fault overload caused by the transferred flow from a removed line may lead to incorrect operation of zone 3 distance protection, which is considered as the origin of several well-known cascading trips. Taking advantage of wide area measurement system (WAMS), a novel scheme is proposed to identify flow transferring to block the zone 3 distance relays which may operate incorrectly. The new voltage and current criteria to distinguish between internal short-circuit fault and non-fault overload caused by transferred flow are derived by use of power system fault modeling. The implementation process is also provided. The simulation results demonstrate the validity of the proposed scheme.
机译:随着电力网络互连的推广,传输线路靠近它们的极限。由移除的线路的传输流引起的可能的非故障过载可能导致区域3距离保护的不正确操作,该距离保护被认为是几个众所周知的级联旅行的起源。利用宽面积测量系统(WAMS),提出了一种新颖的方案来识别流动转移以阻止区域3距离中继,这可能不正确地操作。通过使用电力系统故障建模导出了通过使用电力系统故障建模来源的新电压和电流标准。还提供了实施过程。仿真结果表明了拟议方案的有效性。