首页> 外文会议>International Conference on Electrical Machines and Systems >Inrush current analysis for switching large shunt capacitor bank in a 230 kV substation system
【24h】

Inrush current analysis for switching large shunt capacitor bank in a 230 kV substation system

机译:230 kV变电站系统中切换大型并联电容器组的浪涌电流分析

获取原文

摘要

This paper presents the simulation and investigation of switching large shunt capacitor bank in a 230kV Thailand substation system. Simulation is performed using PSCAD/EMTDC. The inrush current is generated by energizing of the 4×72 Mvar, 230 kV shunt capacitor banks. The purpose is to observe the inrush current to ensure safe and successful operations of the shunt capacitor banks. In addition, the effects of parameters such as sizing of current limiting reactor (CLR), pre-insert resistor (PIR) and 6% detuning reactor are investigated. The results of simulations are shown that the 6% detuning reactor can reduce inrush current more than other methods.
机译:本文介绍了在230kV泰国变电站系统中切换大型并联电容器组的仿真和研究。使用PSCAD / EMTDC执行仿真。浪涌电流是通过为4×72 Mvar,230 kV并联电容器组通电而产生的。目的是观察浪涌电流,以确保并联电容器组安全且成功地运行。此外,还研究了诸如限流电抗器(CLR),预插入电阻器(PIR)和6%失谐电抗器尺寸之类的参数的影响。仿真结果表明,6%失谐电抗器比其他方法能更有效地减小涌入电流。