首页> 外文会议>Annual Pulp and Paper Industry Technical Conference >DESIGN AND APPLICATION OF LOW RATIO HIGH ACCURACY SPLIT-CORE, CORE-BALANCE CURRENT TRANSFORMER
【24h】

DESIGN AND APPLICATION OF LOW RATIO HIGH ACCURACY SPLIT-CORE, CORE-BALANCE CURRENT TRANSFORMER

机译:低比率高精度分芯,核心平衡电流变压器的设计与应用

获取原文
获取外文期刊封面目录资料

摘要

The paper describes the design and application of a split-core CT of large dimensions, specifically designed for mounting in 13.8 kV switchgear cubical on the phase bus bars. Though split-core CT's of high current ratio are available, the authors believe that the core-balance CT described in this paper is unique, as no similar CT was readily available in the US/European market. Thus, there is no equivalent installation in the industry of the specifications described in the paper. The CT discussed in this paper was specifically designed to meet the requirements of dimensions and accuracy for sensitive ground fault and directional ground fault relaying.
机译:本文介绍了大尺寸的分流芯CT的设计和应用,专门用于在相位汇流条上安装在13.8 kV开关设备中。虽然可用的高电流比率的分裂核心CT,但作者认为本文中描述的核心平衡CT是独一无二的,因为美国/欧洲市场上没有类似的CT。因此,在论文中描述的规格的行业中没有等效的安装。本文讨论的CT专门设计用于满足敏感接地故障和定向接地故障中继的尺寸和精度的要求。