Coordination between supply power converters and contactors for fault protection in multi-terminal MVDC distribution systems

机译:多终端MVDC配电系统中电源转换器和接触器之间的协调

获取原文

摘要

We present a fast and effective method for detecting and isolating faults in multi-terminal medium voltage dc shipboard power distribution systems. This new detection method permits coordination between the power supply converters and a set of bus segmentizing contactors without requiring fast communication between the elements. The power converters go into current-limiting mode as soon they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when deciding whether or not to trip in order to isolate the faulted section (later fine tuning can rely on communications). Simulation and experimental results show that faults can be isolated within 10 to 20 ms and the system can be re-energized within 40 to 60 ms.
机译:我们提出了一种快速有效的方法,用于检测和隔离多端介质电压DC船用配电系统中的故障。 该新检测方法允许电源转换器和一组总线分段接触器之间的协调,而无需在元件之间快速通信。 电源转换器一旦识别出故障状况,并且分割接触器就会基于局部跟踪曲线的局部解释作为表观电路电阻的函数来自主决定是否打开的分割接触器。 此方法允许转换器和接触器在决定是否跳闸时仅使用本地测量,以便隔离故障部分(后来的微调可以依赖通信)。 仿真和实验结果表明,故障可以在10到20毫秒内隔离,系统可以在40到60毫秒内重新激活。