首页> 外文会议>Progress in electromagnetics research symposium >Inductive Coupling between Wires in Cables with a Grounded Conductor
【24h】

Inductive Coupling between Wires in Cables with a Grounded Conductor

机译:带接地导体的电缆之间的电感耦合

获取原文

摘要

The arrangement of conductors in a multi-core power cable leads to a situation where various conductor loops are built up. One or several loops are formed by the phase and neutral conductors with the operational current flowing in these conductors. A further loop is built up by the protective earth conductor which is connected to the equipotential bonding system at several locations. The area of this loop is essentially arranged outside of the power cable. The inductive coupling from the phase conductor loops into that loop causes common mode voltages in the protective earth system with consequent common mode currents. It can be demonstrated that this effect takes place even in case of balanced phase currents in the cable. Numerical simulations and parameter studies were carried out in order to describe this effect quantitatively and to investigate the influence of different cable parameters onto the resulting common mode voltages.
机译:多核电源线中的导体的布置导致建立各种导体环的情况。通过相位和中性导体形成一个或多个环,其具有在这些导体中流动的操作电流。通过保护地线导体构建另一环,该保护接地导体在若干位置连接到等电位键合系统。该环的面积基本上布置在电力电缆外部。从相导体环中的电感耦合到该环路中导致保护地球系统中的共模电压,其具有随后的共模电流。可以证明这种效果即使在电缆中平衡的相电流的情况下也发生。进行数值模拟和参数研究,以定量描述这种效果,并研究不同电缆参数对所得的共模电压的影响。