Due to the poor working conditions, the three-core distribution cables are prone to faults. Since most of the cables are laid underground, accurate fault location is difficult. Considering the couplings between the earth screen and core conductors, a lump-parameter model of the three-core cable is constructed in this paper. Through the steady-state circuit analysis, a method for identifying and locating a fault in the three-core cable is proposed. In the method, the information of the grounding line current, core current and voltage phasors at both terminals in normal operation are firstly used to compensate the synchronous measurement error. Then, the fault current is derived by the phase-corrected phasors in fault condition to identify the fault conductor. Finally, the accurate fault distance is computed by employing the fault voltage continuity criterion. A three-core distribution cable model is created by RTDS and various fault simulations are conducted. The results demonstrate the effectiveness of the method under different fault conditions.
机译:由于工作条件差,三核分配电缆容易出现故障。由于大多数电缆都是铺设的,因此精确的故障位置很难。考虑到地球屏幕和核心导体之间的联轴器,本文构建了三芯电缆的块参数模型。通过稳态电路分析,提出了一种用于识别和定位三核电缆故障的方法。在该方法中,首先使用正常操作中两个端子处的接地线电流,芯电流和电压相位的信息来补偿同步测量误差。然后,故障电流通过相位校正的相位器在故障条件下导出以识别故障导体。最后,通过采用故障电压连续性标准来计算精确的故障距离。通过RTD创建三核分布电缆模型,并进行各种故障模拟。结果证明了该方法在不同故障条件下的有效性。

著录项

  • 来源
    《International journal of electrical power and energy systems》 |2021年第9期|106953.1-106953.23|共23页
  • 作者单位

    China Univ Min & Technol Sch Elect & Power Engn Xuzhou 221116 Jiangsu Peoples R China;

    China Univ Min & Technol Sch Elect & Power Engn Xuzhou 221116 Jiangsu Peoples R China;

    China Univ Min & Technol Sch Elect & Power Engn Xuzhou 221116 Jiangsu Peoples R China|Huaiyin Inst Technol Sch Automat Huaian 223003 Jiangsu Peoples R China;

    China Univ Min & Technol Sch Elect & Power Engn Xuzhou 221116 Jiangsu Peoples R China;

    Univ York Dept Elect Engn York YO10 5DD N Yorkshire England;

    State Grid Int Dev Co Ltd SGID Beijing 100031 Peoples R China;

    State Grid Xu Zhou Power Supply Co Xuzhou 221005 Jiangsu Peoples R China;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Mutual coupling; Lump-parameter model; Fault location; Three-core cables;

    机译:互联耦合;块参数模型;故障位置;三芯电缆;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号