首页> 外文会议>ASME summer heat transfer conference >HOT WATER COOLED ELECTRONICS FOR HIGH EXERGETIC UTILITY
【24h】

HOT WATER COOLED ELECTRONICS FOR HIGH EXERGETIC UTILITY

机译:高效能的热水冷却电子

获取原文

摘要

Cooling poses as a major challenge in the IT industry because recent trends have led to more compact and energy intensive microprocessors. Typically microprocessors in current consumer devices and state-of-the-art data centers are cooled using relatively bulky air cooled heat sinks. The large size heat sinks are required due to the poor thermophysical properties of air. In order to compensate for the poor thermal properties of air, it is typical to use chillers to pre-cool the air below the ambient temperature before feeding it to the heat sinks. Operating the chillers requires additional power input thereby making the cooling process more expensive. The growing cooling demand of electronic components will, however, render these cooling techniques insufficient. Direct application of liquid-cooling on chip level using directly attached manifold microchannel heat sinks reduces conductive and convective resistances, resulting in the reduction of the thermal gradient needed to remove heat. Water is an inexpensive, nontoxic and widely available liquid coolant. Therefore, switching from air to water as coolant enables a much higher coolant inlet temperature without in any way compromising the cooling performance. In addition, it eliminates the need for chillers and allows the thermal energy to be reused. All these improvements lead to higher thermal efficiency and open up the possibility to perform electronic cooling with higher exergetic efficiency. The current work explores this concept using measurements and exergetic analyses of a manifold microchannel heat sink and a small scale, first of its kind, hot water cooled data center prototype. Through the measurements on the heat sink, it is demonstrated that the heat load in the state-of-the-art microprocessor chips can be removed using hot water with inlet temperature of 60 °C. Using hot water as coolant results in high coolant exergy content at the heat sink outlet. This facilitates recovering the energy typically wasted as heat in data centers, and can therefore result in data centers with minimal carbon footprint. The measurements on both the heat sink and the data center prototype strongly attest to this concept. Reuse strategies such as space heating and adsorption based refrigeration were tested as potential means to use the waste heat from data centers in different climates. Application-specific definitions of the value of waste heat were formulated as economic measures to evaluate potential benefits of various reuse strategies.
机译:冷却是IT行业的主要挑战,因为最近的趋势导致了更紧凑,更耗能的微处理器。通常,当前的消费类设备和最新数据中心中的微处理器是使用相对笨重的空气冷却散热器来冷却的。由于空气的热物理性能差,因此需要大尺寸的散热器。为了补偿空气的不良热性能,通常在将空气供入散热器之前,先使用冷却器将空气预冷至低于环境温度。操作冷却器需要额外的功率输入,从而使冷却过程更加昂贵。然而,对电子部件的不断增长的冷却需求将使这些冷却技术不足。使用直接连接的歧管微通道散热器在芯片级直接应用液体冷却可降低传导和对流电阻,从而降低去除热量所需的热梯度。水是一种廉价,无毒且可广泛使用的液体冷却剂。因此,从空气切换为水作为冷却剂可实现更高的冷却剂入口温度,而丝毫不影响冷却性能。此外,它消除了对冷却器的需求,并允许热能被重新利用。所有这些改进导致更高的热效率,并开辟了以更高的能量效率进行电子冷却的可能性。当前的工作是通过对歧管微通道散热器和小规模的第一个热水冷却数据中心原型进行测量和充分分析来探索这一概念的。通过对散热器的测量,可以证明,可以使用入口温度为60°C的热水去除现有微处理器芯片中的热负荷。使用热水作为冷却剂会导致散热器出口处的高冷却剂火用含量。这有助于回收通常在数据中心浪费的热量,因此可以使数据中心的碳足迹降至最低。散热器和数据中心原型上的测量结果都充分证明了这一概念。测试了诸如空间加热和基于吸附的制冷之类的重用策略,作为在不同气候下利用来自数据中心的废热的潜在手段。废热价值的特定应用定义被制定为经济措施,以评估各种再利用策略的潜在利益。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号