NUMERICAL STUDY ON THE REDUCTION OF RECIRCULATION USING SEALED COLD AISLES AND ITS EFFECTS ON THE EFFICIENCY OF THE COOLING INFRASTRUCTURE

机译:密封冷通道减少回风的数值研究及其对冷却基础设施效率的影响

获取原文

摘要

The increase in computing performance of electronic equipment is causing higher power consumption and in turn higher heat dissipation. On the larger scale, data centers that house hundreds of these individual electronic equipment are foreseeing an inevitable increase in heat dissipation on a facility level. The cooling cost of these rooms is becoming a major challenge, where a specified inlet temperature must not be exceeded in order to insure the safe and reliable operation of the electronic equipment. Most of the data centers in use today adopt the hot aisle-cold aisle configuration, where air is supplied through a plenum. The major problem with this configuration is the mixing of cold supply air from the tiles with hot exhaust air from the servers. This affects the efficiency of the cooling infrastructure and in turn affects the cost of operation. This study concentrates on the idea of sealing the cold aisle. Completely sealing the cold aisle is not practical due to pressure and noise problems, and therefore a perforated ceiling is proposed. A parametric study is generated to look at the effects of perforated ceiling resistance and different CRAC (Computer Room Air Conditioning) airflow supply percentage on the inlet temperature of the racks. A metric is proposed to quantify the variation of inlet temperature across the height of a rack and for a given cold aisle.
机译:电子设备的计算性能的提高导致更高的功耗,进而导致更高的散热。从更大的角度来看,容纳数百个此类单个电子设备的数据中心可以预见,设备级别的散热不可避免地会增加。这些房间的制冷成本正成为一项主要挑战,为了确保电子设备的安全可靠运行,不得超过规定的入口温度。当今使用的大多数数据中心都采用热通道-冷通道配置,其中空气通过通风道供气。这种配置的主要问题是来自瓷砖的冷供气与来自服务器的热排风的混合。这影响了冷却基础设施的效率,进而影响了运营成本。这项研究集中于密封冷通道的想法。由于压力和噪音问题,完全密封冷通道是不切实际的,因此提出了一种穿孔的天花板。进行了参数研究,以研究穿孔的天花板阻力和不同的CRAC(计算机机房空调)气流供应百分比对机架入口温度的影响。对于给定的冷通道,提出了一种度量来量化整个机架高度上入口温度的变化。

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号