Analysis of the UHV Tie Line Active Power Peak Value of Weak Interconnected Grids Following Power Shortage Disturbance in China Power System

机译:中国电网欠缺扰动后超互联电网特高压联络线有功峰值分析

获取原文

摘要

An ultra high voltage (UHV) AC tie line that connects North China and Central China power grid has been put into operation in 2009. This paper presents a method to calculate the peak value of active power oscillation of the UHV AC tie line following power shortage disturbance. The typical process of the oscillation on the UHV AC line is analyzed. It is shown that the active power oscillation on tie line of week connection grid is similar with the step response of the second-order system. The oscillation peak value is closely related to fault location, system inertia, and system inter-area damping. The method and analysis are tested in China system.
机译:连接华北和华中电网的超高压交流联络线已于2009年投入运营。本文提出了一种计算电力不足后超高压交流联络线有功振荡峰值的方法。骚乱。分析了特高压交流线路的典型振荡过程。结果表明,每周连接电网联络线上的有功功率振荡与二阶系统的阶跃响应相似。振荡峰值与故障位置,系统惯性和系统区域间阻尼密切相关。该方法和分析在中国系统中进行了测试。