首页> 外文会议>International conference on technology of architecture and structure >Study on the Adjustment Law of Supply Water Temperature of the Fan Coil Unit Based on Daily Air-conditioning Load
【24h】

Study on the Adjustment Law of Supply Water Temperature of the Fan Coil Unit Based on Daily Air-conditioning Load

机译:基于日空调负荷的风机盘管给水温度调节规律研究

获取原文

摘要

A new adjustment law of supply water temperature of heat pump unit was presented by analyzing heat transfer performance and computing supply water temperature of fan coil unit (FCU) in this paper. The paper established the energy equations for air side, water side and FCU in dry and wet conditions, respectively. And the heat transfer performance of FCU was obtained by analyzing the manufacturers' performance data. According to an actual central airconditioning system of residential buildings, we calculated the daily inlet water temperature of FCU and proposed the adjustment law for supply water temperature. The results show that the supply water temperature of cooling design day is 9.3°C, the daily supply water temperature of cooling season is higher than 7°C;the supply water temperature of heating design day is 36.4°C, the highest in heating season is 38.5°C, which is below the rated supply water temperature of heat pump unit, 45°C.
机译:通过分析传热性能并计算风机盘管机组的给水温度,提出了一种新的热泵机组给水温度调节规律。本文分别建立了干燥和潮湿条件下空气侧,水侧和FCU的能量方程。通过分析制造商的性能数据,获得了FCU的传热性能。根据住宅的实际中央空调系统,我们计算了FCU的每日进水温度,并提出了供水温度的调节规律。结果表明:制冷设计日的供水温度为9.3°C,制冷季节的日供水温度高于7°C;供暖设计日的供水温度为36.4°C,是供暖季节最高的。温度为38.5°C,低于热泵机组的额定供水温度45°C。