The paper deals with the clarification of basic terms related to the calculation of the earth potential rise (EPR), transferred potential and earth resistance of the earthing grid. In case of earth fault occurring in a substation, significant fraction of the fault current is flowing in the passive conductors (cable sheath, earth wire) of the lines feeding to the fault. These passive conductors are referred to as “return conductors”. Only the remaining fraction of the fault current, i.e. the “equivalent earth current” is passing through the earthing grid entering into the earth. Furthermore, the substation earth is composed of not only from the earth resistance of the grid itself but also the driving point impedance of the passive earthed conductors (other than the return conductors). The parallel resultant of these two is referred to as “equivalent earth resistance” of the substation. The EPR of the substation is given as the product of the equivalent earth current and the equivalent earth resistance.
机译:本文着眼于与接地电势上升(EPR),转移电势和接地网的接地电阻的计算有关的基本术语的澄清。如果变电站发生接地故障,则故障电流的很大一部分将流入馈入故障的线路的无源导体(电缆护套,接地线)中。这些无源导体被称为“返回导体”。故障电流的仅剩余部分,即“等效接地电流”正在流经接地网,并进入大地。此外,变电站的接地不仅由电网本身的接地电阻构成,还由无源接地导体(除返回导体以外)的驱动点阻抗组成。这两者的并联结果称为变电站的“等效接地电阻”。变电站的EPR由等效接地电流和等效接地电阻的乘积给出。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号