摘要

The increased use of cable systems in power distribution in urban areas lead to the need for more reliable cable system. To ensure the reliability of the cable system, a diagnostic system that can assess the cable system in field conditions is needed. Partial Discharge (PD) and Tan Delta (TD) are the two parameters that can be measured to diagnose the condition of cable system in the field. Based on the measurement of these parameters, the condition of cable system can be determined whether the cable is in good condition, needs attention or in bad condition. In this paper the methods of PD and TD field measurement on 20 kV cable systems are described. Furthermore, the method of analysis using data obtained from the measurement of PD and TD is also described. PD measurement in this study is performed using damped AC voltage source (DAC), while TD measurement is carried out by using Very Low Frequency voltage source (VLF). In the end an assessment scheme is proposed for cable diagnostic that can be served as a guideline for Condition Based Maintenance (CBM) of cable system. This scheme will increase not only the reliability of cable system but also the performance of power distribution network.
机译:在城市地区配电中越来越多地使用电缆系统导致需要更可靠的电缆系统。为了确保电缆系统的可靠性,需要一种可以在现场条件下评估电缆系统的诊断系统。局部放电(PD)和损耗角正切(TD)是可以用来诊断现场电缆系统状况的两个参数。基于这些参数的测量,可以确定电缆系统的状况是电缆状况良好,需要注意还是状况不良。本文介绍了在20 kV电缆系统上进行PD和TD现场测量的方法。此外,还描述了使用从PD和TD的测量获得的数据进行分析的方法。本研究中的PD测量是使用阻尼交流电压源(DAC)进行的,而TD测量是使用甚低频电压源(VLF)进行的。最后,提出了一种用于电缆诊断的评估方案,可以用作电缆系统的基于状态的维护(CBM)的指南。该方案不仅可以提高电缆系统的可靠性,而且可以提高配电网的性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号