首页> 外文会议>2011 International Conference on Electric Information and Control Engineering >Study of fault line selection in the non-solidly earthed network based on the method of increasing the grounding capacitance of the line
【24h】

Study of fault line selection in the non-solidly earthed network based on the method of increasing the grounding capacitance of the line

机译:基于增加线路接地电容方法的非固网接地故障选线研究

获取原文
获取外文期刊封面目录资料

摘要

Because of the weak fault current and unstable fault arc, the problems of the single phase to ground fault line selection in the non-solidly earthed network have never been effectively resolved. This paper presents a new method to detect the ground fault line by increasing the grounding capacitance of the lines. If the grounding capacitance of the lines increased, the zero sequence current and the zero sequence capacitance of the fault phase would be increased obviously and the difference between healthy lines and fault line would be increased more obviously. This method resolve the problem of detecting fault line based on zero sequence current and parameter identify, which is high interference, unresponsive and low precision. This method has been verified via an EMTP simulator. The results confirmed that the method is right, effective and low influence to the power system.
机译:由于故障电流弱,故障电弧不稳定,在非固体接地网络中单相接地故障选线的问题一直没有得到有效解决。本文提出了一种通过增加线路的接地电容来检测接地故障线的新方法。如果线路的接地电容增加,则故障相的零序电流和零序电容会明显增加,而健康线与故障线之间的差异会更加明显。该方法解决了基于零序电流和参数识别的故障线检测问题,该方法干扰大,反应迟钝,精度低。该方法已通过EMTP模拟器进行了验证。结果表明,该方法正确,有效,对电力系统影响小。