Through analyzing the characteristic of heat pump and water chiller, the method of replacing the chiller with heat-source heat pump was proposed. Low-freezing solution in the tower was used as refrigeration medium to absorb heat from the air, and condenser was utilized to supply heat water for the user. As the key device for gaining heat from the ambient, heat-source tower played an important role in the whole system. Therefore the experiment was done on the cross-flow packing in the heat-source tower, and results showed that: improving the difference of inlet solution temperature and ambient temperature, the heat transfer of heat-source tower straightened up and at the same time the absorbent solution volume soared. Increasing the air flow rate and solution flow rate, the heat transfer raised but became slowly. Raising the air flow rate could reduce the entrance of water-vapor condensed from the air to some extent, while increasing the solution flow rate could absorb more water-vapor in large part.
机译:通过分析热泵和冷水机的特点,提出了用热源热泵代替冷水机的方法。塔中的低冻结溶液用作制冷剂,以吸收空气中的热量,冷凝器用于为用户提供热水。作为从环境中获取热量的关键设备,热源塔在整个系统中起着重要的作用。因此,对热源塔的错流填料进行了实验,结果表明:改善了入口溶液温度和环境温度之间的差异,使热源塔的传热趋于平直,同时热源塔的传热得到了改善。吸收剂溶液的体积猛增。空气流量和溶液流量增加,传热增加,但变慢。提高空气流量可以在一定程度上减少空气中凝结的水蒸气的进入,而增加溶液流量可以在很大程度上吸收更多的水蒸气。