首页> 外文会议>International Conference on Electrical and Control Engineering >De-icing Schemes and Operations for Overhead Power Line Based on Shunt Capacitor Over-compensation Method
【24h】

De-icing Schemes and Operations for Overhead Power Line Based on Shunt Capacitor Over-compensation Method

机译:基于并联电容器过补偿法的架空电力线除冰方案与运行

获取原文

摘要

De-icing schemes and operations for overhead power line in 10kV, 66kV and 220kV networks based on shunt capacitor over-compensation method are proposed in this paper. This novel de-icing method is based on characteristics of sinusoidal AC and theory of shunt capacitor over-compensation. By utilizing 10kV capacitor bank, which is installed as standard apparatus in substation, reactive current can be transmitted to the specific de-icing power line, which leads to over-compensation of network, and temperature of the power line will be increased. This de-icing scheme and operations are proved and verified in 10kV network by on-site experiments. Focus on characteristics and structure of power grid in China, this method is feasible to transferred and applied in 35kV, 66kV and 220kV networks.
机译:提出了基于并联电容器过补偿法的10kV,66kV,220kV架空电力线路除冰方案和运行方法。这种新颖的除冰方法基于正弦交流电的特性和并联电容器过补偿的理论。通过使用作为变电站标准设备安装的10kV电容器组,无功电流可以传输到特定的除冰电力线,这会导致网络的过度补偿,并且电力线的温度会升高。通过现场实验在10kV电网中验证了该除冰方案和操作。着眼于中国电网的特点和结构,该方法在35kV,66kV和220kV电网中的转移和应用是可行的。