首页> 外文会议>2010 5th International Conference on Critical Infrastructure >Study on method of single-phase-to-earth fault section location in neutral point resonant grounded system
【24h】

Study on method of single-phase-to-earth fault section location in neutral point resonant grounded system

机译:中性点谐振接地系统单相接地故障段定位方法研究

获取原文

摘要

Due to the large amount of branches and high grounding resistance of the distribution network, the earth fault location has not been solved effectively. A live location method is proposed for the single-phase-to-earth fault section in the neutral point resonant grounded system. By this method, the compensation current of arc-suppression coil is adjusted after the metallic earth fault occurs. And the fault section can be confirmed by the variation of zero-sequence current measured by FTU equipped in the lines, for the zero-sequence current in the non-fault path is proportional to the zero-sequence voltage. When the single-phase-to-earth fault via resistance occurs, zero-sequence voltage changes after the arc-suppression coil is adjusted. The method is also effective as long as the zero-sequence current is converted by zero-sequence voltage. The site experiments have been carried out to prove that the method is feasible.
机译:由于分配网络的大量分支和高接地电阻,地球故障定位尚未有效地解决。为中性点谐振接地系统中的单相位接地故障部分提出了实时位置方法。通过这种方法,在金属接地故障发生后调整了弧形抑制线圈的补偿电流。并且故障部分可以通过通过配备在线的FTU测量的零序电流的变化来确认,对于非故障路径中的零序电流与零序电压成比例。当通过电阻发生单相到接地故障时,调节弧形抑制线圈后的零序电压变化。只要通过零序电压转换零序电流,该方法也是有效的。已经进行了现场实验以证明该方法是可行的。