A closed-loop impingement spray cooling system which is capable of cooling a 1kW 6U electronic test card has been developed. The heated surface area is 13.5 × 15.1 cm2. R134a was used as working fluid in a modified refrigeration closed-loop cycle. Four vapor assisted nozzles are implemented to generate spray to cover a large ratio of the heated area of the card. The effects of mass flow rate and spray saturation temperature on thermal performance are investigated experimentally in this study. Experimental results are promising with a stable average temperature of around 25 C being maintained on the heated surface with small temperature variation on the heated surface at suitable operating conditions. It is found that cooling performance has been improved with increasing of mass flow rate and spray saturation temperature.
机译:已经开发出一种能够冷却1kW 6U电子测试卡的闭环冲击喷雾冷却系统。加热的表面积为13.5×15.1 cm 2 。 R134a在改进的制冷闭环循环中用作工作流体。四个蒸汽辅助喷嘴用于产生喷雾,以覆盖卡的大部分受热区域。本研究通过实验研究了质量流量和喷雾饱和温度对热性能的影响。实验结果很有希望,在合适的工作条件下,在加热表面上保持约25℃的稳定平均温度,在加热表面上保持较小的温度变化。发现随着质量流量和喷雾饱和温度的增加,冷却性能得到了改善。