Based on the power system simulation software DIgSILENT, this paper presents the Electro-Magnetic Transient (EMT) simulation of Very Fast Transient Overvoltage (VFTO) phenomena in 500kV GIS substation of Xiangshuijian pumped storage power station. The modeling of GIS components and its connected equipments are summarized. The operation of disconnector in GIS under different typical substation configurations is simulated. It is concluded that the highest VFTO level in the GIS substation is below 500kV substation Lightning Impulse Withstand Voltage (LIWV). The influence factors of VFTO are studied in this paper, including transformer entrance capacitance, residual charge of GIS bus conductor and the cable length between GIS and transformer. The variation regularities of VFTO level with these factors are concluded.
机译:基于电力系统仿真软件DIgSILENT,介绍了响水尖抽水蓄能电站500kV GIS变电站的超瞬态过电压(VFTO)现象的电磁瞬态(EMT)仿真。总结了GIS组件及其连接设备的建模。在不同的典型变电站配置下,对GIS中隔离开关的操作进行了仿真。结论是GIS变电站的最高VFTO等级低于500kV变电站的雷电冲击耐受电压(LIWV)。研究了VFTO的影响因素,包括变压器的入口电容,GIS总线导体的剩余电荷以及GIS与变压器之间的电缆长度。得出了VFTO水平随这些因素的变化规律。