首页> 外文期刊>Meiden Review: International Edition >Transformer and generator models useful for transferred voltage analysis for power stations and substations
【24h】

Transformer and generator models useful for transferred voltage analysis for power stations and substations

机译:变压器和发电机模型可用于电站和变电站的转移电压分析

获取原文
获取原文并翻译 | 示例
       

摘要

We have successfully developed a transformer model of transferred voltage based on the data of transferred voltage obtained from measurements. It is universally useful for the accurate analysis of transformer transferred voltage waveforms, obtainable only from the rated quantities of a transformer and test data. Also for the generator model, we have developed a model based on the measurements when a generator is connected, enabling the accurate analysis of transferred voltage waveforms obtainable only from the rated quantities of the generator and general test data. If our models are adequately applied, they can solve the problems of resonance overvoltages that have been under study recently. They can be used for more dynamic lightning surge analysis, inclusive of the behavior of equipment connected to the low-voltage side of the transformer. We believe that they are very useful in the search for more dependable insulation coordination.
机译:我们已经根据测量获得的传输电压数据成功开发了传输电压的变压器模型。它对于准确分析变压器传递的电压波形非常有用,该波形只能从变压器的额定量和测试数据中获得。此外,对于发电机模型,我们还基于发电机连接时的测量值开发了一个模型,从而可以准确分析仅从发电机的额定量和常规测试数据中获得的传输电压波形。如果我们的模型得到充分应用,它们可以解决最近正在研究的谐振过电压问题。它们可用于更动态的雷电浪涌分析,包括连接到变压器低压侧的设备的性能。我们认为,它们在寻求更可靠的绝缘配合方面非常有用。