首页> 外文会议>2010 North American Power Symposium >Adaptive harmonic estimation technique for reduction the blocking time of transformer for differential protection
【24h】

Adaptive harmonic estimation technique for reduction the blocking time of transformer for differential protection

机译:减少谐波差动保护闭锁时间的自适应谐波估计技术

获取原文

摘要

This paper presents a new adaptive methodology for 2nd harmonic estimation of transformer differential protection in order to reduce the blocking time of transformer in inrush condition. The proposed algorithm provides a useful tool for signal estimation in non-sinusoidal power system such as faulty conditions or switching time. This method employs a variable window length algorithm for signal estimation, which is extended through time passing, and uses only post-fault data for signal estimation. Also, conventional Discrete Fourier Transform (DFT) was compared to this method. Moreover, the simulated results presented clearly, the proposed algorithm can accurately estimates the 2nd harmonic in less time than conventional methods like conventional DFT.
机译:本文提出了一种新的自适应方法,用于变压器差动保护的二次谐波估计,以减少浪涌条件下变压器的堵转时间。所提出的算法为非正弦电力系统中的信号估计提供了有用的工具,例如故障条件或开关时间。该方法采用可变窗口长度算法进行信号估计,该算法会随着时间的流逝而扩展,并且仅将故障后数据用于信号估计。此外,将传统的离散傅立叶变换(DFT)与该方法进行了比较。此外,仿真结果清楚地表明,与传统的DFT等传统方法相比,该算法可以在更短的时间内准确估计出2 nd 谐波。