首页> 外文会议>2010 International Conference on Industrial Electronics, Control Robotics >Comparative study of different controllers for automatic generation control of an interconnected hydro-thermal system with generation rate constraints
【24h】

Comparative study of different controllers for automatic generation control of an interconnected hydro-thermal system with generation rate constraints

机译:具有发电量约束的互联水热系统自动发电控制中不同控制器的比较研究

获取原文

摘要

This paper compares the conventional integral, fuzzy and hybrid neuro-fuzzy (HNF) controllers for the automatic generation control (AGC) of an interconnected hydro-thermal system. The design objective is to improve the transient performance of the interconnected system following a disturbance. Appropriate generation rate constraint (GRC) has been considered for the thermal and hydro plants. In the analysis, the hydro area has been considered with electric governor and thermal has been considered with single reheat turbine. System performance has been examined considering 1% step load perturbation in either thermal or hydro area with generation rate constraints. Simulation results are presented to show the improved performance of HNF controller in comparison with a conventional integral and fuzzy controller.
机译:本文比较了传统的积分,模糊和混合神经模糊(HNF)控制器的互连水热系统的自动发电控制(AGC)。设计目标是在出现干扰后改善互连系统的瞬态性能。对于火力发电厂和水力发电厂,已经考虑了适当的发电率约束(GRC)。在分析中,水力区域已考虑使用电调速器,热力已考虑使用单个再热式涡轮机。已经考虑了在热或水力区域受发电速率约束的1%阶跃负载扰动对系统性能的检查。仿真结果表明,与传统的积分和模糊控制器相比,HNF控制器的性能有所提高。