首页> 外文会议>2010 Annual Report Conference on Electrical Insulation and Dielectric Phenomena >Effect of absolute humidity on disruptive discharge voltage of standard sphere air gaps
【24h】

Effect of absolute humidity on disruptive discharge voltage of standard sphere air gaps

机译:绝对湿度对标准球形气隙破坏性放电电压的影响

获取原文

摘要

The existing IEC standard prescribes humidity correction method of disruptive discharge voltage of standard sphere gaps, which is derived from experimental data under absolute humidity between 5 g/m3 and 12 g/m3. However, higher humidity is experienced in summer in Japan and also all over a year in tropical countries. In the present study, validity of the existing correction method is discussed for application up to 22 g/m3 based on a series of experiments for several years under natural humidity condition.
机译:现有的IEC标准规定了标准球间隙的破坏性放电电压的湿度校正方法,该方法是根据在5 g / m 3 和12 g / m 3 的绝对湿度下的实验数据得出的。 sup>。但是,在日本的夏季以及热带国家,一年四季的湿度都较高。在本研究中,基于在自然湿度条件下进行的数年实验,讨论了现有校正方法在高达22 g / m 3 的应用中的有效性。