首页> 外文会议>Universities Power Engineering Conference (UPEC), 2009 >A new transient current based centralized selectivity algorithm for earth faults in isolated and compensated neutral MV networks
【24h】

A new transient current based centralized selectivity algorithm for earth faults in isolated and compensated neutral MV networks

机译:一种新的基于暂态电流的集中式选择性中性算法

获取原文

摘要

This paper presents a new centralized selectivity algorithm for earth-faults in isolated and compensated neutral medium voltage (MV) networks. The algorithm proposes to investigate and utilize the relation between the transient phase current changes in the substation transformer and the transient residual currents for each feeder and section of the network. The transient RMS values of the residual currents for each feeder and section and the transformer phase current changes are calculated, in a constant sliding window of 2.5 ms, using a sampling frequency of 25 kHz. The proposed fault indication levels for each feeder and section will be calculated. The faulted feeder and section can be selected precisely from the higher fault indication levels, without any voltage measurements. The proposed algorithm is valid for isolated and compensated neutral networks. A 20 kV, 251 km medium voltage distribution network is simulated by ATP/EMTP program. Extensive simulations are performed to validate the proposed algorithm.
机译:本文提出了一种新的集中式选择性算法,用于隔离和补偿的中性中压(MV)网络中的接地故障。该算法建议研究并利用变电站变压器中的暂态相电流变化与每个馈线和网络部分的暂态剩余电流之间的关系。在25 ms的恒定滑动窗口中,使用25 kHz的采样频率,计算出每个馈线和各部分的剩余电流的瞬态RMS值以及变压器相电流的变化。将计算每个馈线和各部分的建议故障指示级别。可以从较高的故障指示级别中精确选择有故障的馈线和部件,而无需进行任何电压测量。所提出的算法对于隔离和补偿的中立网络是有效的。通过ATP / EMTP程序模拟了一个20 kV,251 km的中压配电网。进行了广泛的仿真,以验证所提出的算法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号