Analysis of Insulation Aging Performance of Medium Voltage Crosslinked Polyethylene Cable During Operation

机译:中压交联聚乙烯电缆的绝缘老化性能分析

获取原文
获取外文期刊封面目录资料

摘要

In order to explore the characteristics of insulation aging changes of medium voltage cross-linked polyethylene cables after running for a period of time, the dielectric loss of 35 kV cable insulation with new cable and actual operating life of 1a, 3a, 5a, 7a, 10a was studied. Axial slicing was performed on the inside and outside of the cable with different operating years. A flat sample with a surface of 1 mm thickness was prepared and tested. The experimental results show that the low frequency dielectric loss factor of XLPE correlates with the aging degree. When the frequency is below 0.1 Hz, the tangent of dielectric loss angle shows a linear upward trend with the aging degree. The outer dielectric loss of the actual running cable insulation is greater than the inner side, indicating that environmental factors may be the main cause of insulation aging of the running cable. The detection of dielectric loss can evaluate the external environment of the running cable, the main insulation aging cause, and the aging degree. It is a simple and effective method suitable for practical engineering applications.
机译:为了探讨在运行一段时间后探讨中压交联聚乙烯电缆的绝缘老化变化的特点,介电损耗35 kV电缆绝缘电缆和1A,3A,5A,7A的实际工作寿命,研究了10A。在电缆的内部和外部进行轴向切片,具有不同的营业年。制备和测试具有1mm厚的表面的扁平样品。实验结果表明,XLPE的低频介电损耗因子与老化程度相关。当频率低于0.1Hz时,介电损耗角的切线显示出具有老化程度的线性向上趋势。实际运行电缆绝缘的外介电损耗大于内侧,表明环境因素可能是运行电缆绝缘老化的主要原因。介电损耗的检测可以评估运行电缆的外部环境,主要的绝缘老化原因和老化程度。这是一种适用于实用工程应用的简单有效的方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号