Influence factors analysis about terminal voltage of wind turbine when single phase grounding fault occurs

机译:发生单相接地故障时风力涡轮机末端电压的影响因素分析

获取原文
获取外文期刊封面目录资料

摘要

The stator of the doubly fed induction generator is directly connected to the power grid, which is very sensitive to the disturbance of power grid. Wind turbine will take off the network when grid voltage drops because of single-phase fault. It will seriously impact on safe operation of power grid. This paper introduces the requirement of low voltage ride through performance of wind turbine and the effect of power grid fault on the operation of wind turbine generator. Based on the fault component analysis method, the influence factors of the single phase voltage sag of the system are analyzed. The simulation model is built on the PSCAD/EMTDC and the analysis results are verified by simulation.
机译:双馈感应发电机的定子直接连接到电网,对电网的干扰非常敏感。由于单相故障,电网电压下降时,风力涡轮机将取出网络。它会严重影响电网的安全操作。本文介绍了通过风力涡轮机的性能的低电压骑行的要求及电网故障对风力涡轮发电机运行的影响。基于故障分析方法,分析了系统的单相电压凹陷的影响因素。模拟模型基于PSCAD / EMTDC构建,通过模拟验证分析结果。