Analysis of 10kV grid arc grounding over-voltage hazards and countermeasures

机译:10kV网格弧接地过压危险的分析及对策

获取原文

摘要

Through the analysis of 2 single-phase grounding over voltage accidents caused by capacitive over current in 10 kV power grids in this paper, the causes and damages of arc grounding over voltage are illustrated, and the necessity of capacitive current test and effective methods are pointed out. The test and assessment to the 29 substations' capacitor currents provides a scientific basis for the correct selection of the neutral point operation mode, and the strengths and weaknesses of the neutral Point grounding through the arc suppression circle and the mode trends of 10kV grid neutral grounding are demonstrated.
机译:通过分析由电容上的电容上的电压引起的2个单相接机,在本文中的10kV电网中引起的电压引起的电流,射门接地的原因和损坏,并指出了电容性电流测试和有效方法的必要性出去。对29个变电站电容器电流的测试和评估为正确选择中性点操作模式提供了科学依据,以及通过电弧抑制圆圈的中性点接地的强度和弱点以及10kV网格中性接地的模式趋势被证明。