Ferro-resonance over-voltage and power frequency over-voltage onthe neutrals of 220kV power transformer and correspondingprotection strategy

机译:220kV电力变压器中中子的铁谐振过电压和功率频率过电压和相应的保障策略

获取原文

摘要

In order to limit short-circuit current and satisfy the need of relay setting, only part of the 220kV power transformer is grounded, so on the neutrals of ungrounded transformers will appear the over-voltage. Currently the value of over-voltage on transformer neutral point and the corresponding protection strategy is based on theoretical formula, this article use the PSCAD/EMTDC software to calculate the over-voltage on the neutral point of 4 ungrounded power transformers in Chongqing 220kV power grid, the result shows that the power frequency transient over-voltage on the neutrals may reach I78kV, If the single-phase grounding fault occurs in ungrounded power system, the power frequency over-voltage on the neutrals will be more serious and rise to 138.6kV. Non-full phase operation may cause serious ferro-resonance over-voltage on the neutrals of no-load transformer, which may last for seconds and may rise to 723.7kV, causing serious threat to the transformer neutrals and line-side equipment. The article also studies the gap parameter which should be taken on the neutrals of 220kV transformers at the end
机译:为了限制短路电流并满足继电器设置的需要,仅220kV电力变压器的一部分接地,因此在未接地变压器的中性上的中性将出现过电压。目前,变压器中性点的过电压的值和相应的保护策略基于理论公式,本文使用PSCAD / EMTDC软件计算重庆220kV电网4个未接地电力变压器的中性点上的过电压,结果表明,如果在未接地的电源系统中发生单相接机故障,中性的功率瞬态过电压可能会达到I78kV,所以中性的功率频率过电压将更加严重并增加至138.6kV 。非全相运行可能导致空载变压器的中性上的严重铁谐振过电压,这可能持续秒,可能上升到723.7kV,对变压器中性和线路设备产生严重威胁。本文还研究了在最后,应在220kV变压器的中性载体上采取的间隙参数

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号