Application Research on Grounding Resistance Reduction in Substation in High Soil Resistivity Area and with Limited Grounding Area

机译:高土壤电阻率区域变电站接地阻力的应用研究与有限的接地区

获取原文

摘要

This paper introduces the successful application of electrolytic pole in the inclined shafts to reduce the grounding resistance of the original ground grid in order to meet the designed requirements in the reconstruction of an existing substation in high soil resistivity area via the electrolyte generated from the electrolytic pole. The original data of the 500kV Boluo substation of Huizhou in Guangdong China shows that the ground resistance is 1.05Ω and soil resistivity greater than 1000Ω.m. The method involved digging eight inclined shafts with a total length of 1800m in the periphery of the existing ground grid for the placement of 80 sets of electrolytic pole. Results show that the ground resistance reduces to 0.2013Ω, a reduced rate of 80.8% after the completion of the reconstruction project. The paper is intended to provide an effective solution for the design and reconstruction of substation in high soil resistivity areas with limited grounding area yet where ground resistance reduction is required.
机译:本文介绍了电解杆在倾斜轴中的成功应用,以降低原始地面网格的接地电阻,以满足通过电解杆产生的电解质在高土壤电阻率区域的现有变电站的重建中的设计要求。广东惠州500kV Boluo变电站的原始数据表明,地电阻为1.05Ω,土壤电阻率大于1000Ω.m。该方法涉及在现有地面网格的周边挖出八个倾斜轴,总长度为1800米,以放置80组电解杆。结果表明,接地电阻降低至0.2013Ω,重建项目完成后降低80.8%。本文旨在为具有有限接地区域的高土壤电阻率区域的变电站的设计和重建提供有效的解决方案,但是需要接地阻力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号