首页> 外文会议>China International Conference on Electricity Distribution >The Application Research of Very Low Frequency Diagnostic Methods in Acceptance Tests on New Cable Systems of Medium Voltage
【24h】

The Application Research of Very Low Frequency Diagnostic Methods in Acceptance Tests on New Cable Systems of Medium Voltage

机译:非常低频诊断方法在中电缆新电缆系统接受测试中的应用研究

获取原文

摘要

Tangent delta (TD) measurements using very low frequency (VLF) sinusoidal waveform in aged cable system have been proved sensitive to water tree degradation and insulation aging. Whereas, the application of VLF in acceptance tests on new cable systems of medium voltage is still on research and development. This paper presents an experimental study of the capability of the main VLF testing methods for newly installed 10kV XLPE cable systems in acceptance tests. Compared with oscillation wave excitation, the different waveforms including sinusoidal (Sinus) and cosine-rectangular (CR) of VLF voltage were employed to stress the nine samples of artificial defects of different types. Various characteristics of TD measurement and partial discharge (PD) measurement were analyzed. The results showed that VLF-Sinus voltage has a distinctive ability of detection for a wet or lossy accessory through TD or PD measurements. It is recommended to employ a combination of the monitored VLF-Sinus withstand with TD measurement and the PD measurement under damped alternative current (DAC) or VLF-CR as field diagnostic tools in acceptance test for newly installed cables.
机译:使用非常低的频率(VLF)的正弦波形在老化电缆系统的正切δ(TD)测量已被证明水树降解和绝缘老化敏感。然而,VLF在中等电压的新电缆系统验收测试的应用仍然在研究和发展。本文介绍了主要VLF测试方法在验收测试新安装10kV交联电缆系统的能力的实验研究。用振荡波激励相比,不同的波形,包括正弦(窦)和VLF电压的余弦矩形(CR)被用来强调不同类型的人工缺陷的九个样本。 TD测量和局部放电(PD)的测量的各种特性进行了分析。结果表明,VLF-窦电压具有检测用于通过TD或PD测量湿或有损附件的独特能力。建议采用的组合监测VLF-窦承受与TD测量和下阻尼交流(DAC)或VLF-CR作为场诊断工具在验收试验为新安装的电缆的局部放电测量。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号