首页> 外文会议>International Conference on Compressors and Their Systems >Experimental study and optimal control strategy of a transcritical CO2 heat pump water heater
【24h】

Experimental study and optimal control strategy of a transcritical CO2 heat pump water heater

机译:跨临界二氧化碳热泵热水器的实验研究与最优控制策略

获取原文

摘要

In this study,a transcritical CO2 heat pump water heater prototype was experimentally investigated in order to clarify the effects of the opening of electronic expansion valve (EEV),research the optimal discharge pressure and obtain an optimal control strategy for performance optimization.The tests were carried out by regulating the opening of EEV in multiple working conditions.The results showed that the decrease of opening led to reduction in evaporator inlet pressure and gas cooler outlet temperature,augment in discharge temperature,and decrease first then increase in discharge pressure.The optimal opening to reach maximum coefficient of performance (COP) always existed in all working conditions,however,there were two different situations where the corresponding optimal discharge pressure was near or away from the minimal value of the pressure curve.The reason for this phenomenon was the difference in water inlet temperature.Moreover,a correlation for the optimal discharge pressure was established with ambient temperature,water inlet and outlet temperature as independent variables.Furthermore,an optimal control strategy,in which the control of discharge pressure and superheat degree was considered,was proposed based on the correlation.Testing results proved that the optimization of performance could be achieved by using the strategy and the deviations between the COP under the control strategy and the optimal COP measured by experiments were within 5%.
机译:在这项研究中,通过实验研究了跨临界CO2热泵热水器原型,以澄清电子膨胀阀(EEV)的开口,研究最佳排放压力并获得性能优化的最佳控制策略。测试是通过在多个工作条件下调节EEV的开口来执行。结果表明,开口的降低导致蒸发器入口压力和气体冷却器出口温度降低,在排出温度上增加,并首先降低排出压力。最佳开放以达到最大的性能系数(COP)始终存在于所有工作条件下,然而,在所有不同的情况下,相应的最佳排放压力接近或远离压力曲线的最小值。这种现象的原因是进水口温度差异.Oresover,具有最佳排出压力的相关性以环境温度,进水口和出口温度建立为独立的变量。基于相关性,提出了一种基于相关性的最佳控制策略,其中考虑了排出压力和过热程度的控制。结果证明了性能优化可以通过使用策略来实现,并在控制策略下的警察与通过实验测量的最佳警察的偏差在5%以内。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号