首页> 外文会议>Intelligent Control and Automation, 2004. WCICA 2004. Fifth World Congress on >An improved signal processing method for Coriolis mass flowmeter based on time-varying signal model
【24h】

An improved signal processing method for Coriolis mass flowmeter based on time-varying signal model

机译:基于时变信号模型的改进型科里奥利质量流量计信号处理方法

获取原文

摘要

An adaptive IIR notch filter with the capability of tracking frequency variation was applied to filter the sensor output signal, whose frequency, amplitude and phase were time-varying based on the random walk model, of Coriolis mass flow meter and calculates its frequency. An adaptive line enhancer based on the above notch filter extracted the signal we required from noisy data. Then the sliding Goertzel algorithm with overlap windows was used to calculate the real time phase difference between two signals of this kind. With the frequency and phase difference obtained, the time interval of the two signals and the mass flowrate were derived. The simulation results show that algorithms studied in this paper are efficient.
机译:应用具有跟踪频率变化能力的自适应IIR陷波滤波器,对科里奥利质量流量计的传感器输出信号进行滤波,该传感器输出信号的频率,幅度和相位基于随机游动模型随时间变化,并计算其频率。基于上述陷波滤波器的自适应线路增强器从噪声数据中提取了我们所需的信号。然后使用带有重叠窗口的滑动Goertzel算法来计算这种两个信号之间的实时相位差。利用获得的频率和相位差,得出两个信号的时间间隔和质量流量。仿真结果表明,本文所研究的算法是有效的。