首页> 外文会议>Compressors and their Systems >Screw-expressor testing on an R-134a chiller―efficiency, liquid carry-over, and chiller benefit
【24h】

Screw-expressor testing on an R-134a chiller―efficiency, liquid carry-over, and chiller benefit

机译:在R-134a冷水机上进行螺杆式压缩机测试-效率,液体残留和冷水机效益

获取原文

摘要

The expressor concept intends to improve the efficiency of water-cooled R-134a chillers by 6% by harnessing the power of the flashing liquid that is lost during throttling in the standard refrigeration cycle and using this power directly to compress a fraction of the low pressure vapor available after the expansion process. Full-size screw-expressor prototype hardware has been designed and procured by City University London (CUL). Initial prototype testing was performed in the R-113 CUL SPERE test rig at pressures simulating the R-134a chiller conditions.
机译:通过利用在标准制冷循环中的节约过程中损失的闪蒸液体的功率并使用此电源直接压缩低压的一部分,通过利用闪蒸的液体的功率来提高水冷式R-134a冷却器的效率6%。膨胀过程后可用的蒸气。全尺寸螺旋Extress原型硬件由城市大学(CUL)设计和采购。在R-113 CUL SPERE试验台中进行初始原型测试,压力模拟R-134A冷却条件。