The optimal allocation pattern of phase shifting transformers for unwinding parallel flows

机译:解开平行流的移相变压器的最优分配方式

获取原文
获取外文期刊封面目录资料

摘要

This paper proposes a new method to determine the optimal allocation pattern of multiple phase shifting transformers (PSTs) for unwinding parallel flows. In the proposed method, the concept of co-tree in graph theory is used to determine the minimum number of PSTs required for the independent modulation of individual loop flows. Moreover, eigenanalysis is applied to find out the correlation between each allocation patterns of PSTs and corresponding power flow profiles. Consequently, the sensitivity of flow alteration vector to the input angle vector of PSTs can be characterized into a matrix. Whereas, by the sensitive matrix, the required control angles of each PST for unwinding parallel flows can be found precisely. As a result of the proposal, the optimal allocation pattern of PSTs is determined as which can unwind the specific parallel flows by minimum control angles against other patterns. The validity of the proposed method is confirmed through the simulation studies.
机译:本文提出了一种确定用于展开并联流的多相移位变换器(PSTS)的最佳分配模式的新方法。在所提出的方法中,图形理论中的CO树的概念用于确定独立调制各个环路所需的最小PST数。此外,应用了特征分析以找出PST的每个分配模式与相应的功率流程轮廓之间的相关性。因此,可以将流动改变向量与PST的输入角度向量的敏感性表征为矩阵。然而,通过敏感矩阵,可以精确地找到每个PST的所需控制角来展开并行流。作为提议的结果,确定PST的最佳分配模式,其可以通过对其他图案的最小控制角来展开特定的并行流。通过模拟研究确认了所提出的方法的有效性。