首页> 外文会议>Electrical Insulation and Dielectric Phenomena, 2001 Annual Report. Conference on >Research of steep-front wave impulse voltage test effectiveness in finding internal fault of composite insulators
【24h】

Research of steep-front wave impulse voltage test effectiveness in finding internal fault of composite insulators

机译:寻找复合绝缘子内部故障的陡前波脉冲电压测试有效性的研究

获取原文

摘要

In order to verify the effectiveness of steep-front impulse voltage testing in finding the internal faults of composite insulators, some insulators with faults are modeled which include conductive channel, semi-conductive airy channel and partial little air bubbles that occur separately at different places. A steep-front wave impulse voltage test (steepness of wave front is 1000-4000 kV//spl mu/s) is respectively made for these faulty and normal insulators. At the same-time the internal electric field intensity and its distribution in the insulator is calculated by making use of infinite element analysis software in order to test whether breakdown has occurred. The result is consistent with the experimental one. The final result shows that steep-front wave impulse voltage testing plays a very effective part in finding severe faults of the insulator, however, tiny faults are not easy found using this method. The result of this research gives a reference to revise the steep-front wave impulse voltage test standard.
机译:为了验证陡峭前冲电压测试在发现复合绝缘子内部故障中的有效性,对一些有故障的绝缘子进行了建模,包括导电通道,半导电通风通道和在不同位置分别出现的局部小气泡。对这些故障绝缘子和正常绝缘子分别进行了陡峭的波前冲击电压测试(波前的陡度为1000-4000 kV // spl mu / s)。同时,通过使用无限元分析软件计算内部电场强度及其在绝缘子中的分布,以测试是否发生击穿。结果与实验结果一致。最终结果表明,陡峭的前波脉冲电压测试在发现绝缘子的严重故障中起着非常有效的作用,但是,使用这种方法很难发现微小的故障。研究结果为修订陡前波冲击电压试验标准提供了参考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号