首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Steep-front impulse voltage in diagnostic studies of composite insulators
【24h】

Steep-front impulse voltage in diagnostic studies of composite insulators

机译:陡前脉冲电压在复合绝缘子诊断研究中的应用

获取原文
获取原文并翻译 | 示例
           

摘要

Laboratory studies of composite insulators by means of steep-front impulse voltage tests are presented. The tests were performed on four groups of insulators, i.e. on newly manufactured insulators, on insulators removed from service, on insulators earlier exposed to mechanical fatigue test and on insulators with intentionally introduced technological defects. Extensive results of these investigations indicate that application of steep-front impulses of 4 kVs provides a better diagnostic efficiency as compared with the standard testing by means of impulses with steepness of 1 kVs. It is shown that the application of 4 kVs impulses do not cause any damage to healthy insulators, while defected insulators are identified reliably. A new methodology allowing to assess the status of internal insulation in insulators removed from service is proposed based on the performed studies.
机译:介绍了通过陡峭前冲电压测试对复合绝缘子进行的室内研究。测试是在四组绝缘子上进行的,即在新制造的绝缘子上,在退役的绝缘子上,在经受机械疲劳测试的绝缘子上以及在故意引入技术缺陷的绝缘子上进行的测试。这些研究的广泛结果表明,与通过1 kV / ns陡度的脉冲进行标准测试相比,施加4 kV / ns的陡峭前线脉冲可提供更好的诊断效率。结果表明,施加4 kV / ns的脉冲不会对健康的绝缘子造成任何损坏,同时可以可靠地识别出有缺陷的绝缘子。在进行的研究的基础上,提出了一种新的方法,该方法可以评估停止使用的绝缘子的内部绝缘状态。