首页> 外文会议>Electrical Insulating Materials, 2001. (ISEIM 2001). Proceedings of 2001 International Symposium on >Study on the application of an on-line synthetic detecting system for transformer insulation
【24h】

Study on the application of an on-line synthetic detecting system for transformer insulation

机译:在线综合检测系统在变压器绝缘中的应用研究

获取原文

摘要

The on-site synthetic transformer insulation monitoring system, developed by applying the theory of this paper and practically installed on a certain primary 110 kV transformer, can synchronously measure six kinds of gases dissolved in transformer oil (including H/sub 2/, CO, CH/sub 4/, C/sub 2/H/sub 4/, C/sub 2/H/sub 2/, C/sub 2/H/sub 6/), dielectric loss of transformer bush and grounding current of transformer magnet core. The theory of every unit contained in the system is discussed, further more, the on-site data by this system and off-site data by field test are compared according to their respective time point. During its long time steady running period, this monitor system has successfully forenoticed a high temperature overheat fault occurring inside the transformer, the superscales of gases coincide with results from traditional spectrum analysis. In the end, the result of real core-hangout test supported the validity of this system.
机译:通过应用本文理论和实际上安装在某个初级110 kV变压器上的现场合成式变压器绝缘监控系统,可以同步测量溶解在变压器油中的六种气体(包括H / SUB 2 /,CO, CH / SUB 4 /,C / SUB 2 / H / SUB 4 /,C / SUB 2 / H / SUB 2 /,C / SUB 2 / H / SUB 6 /),变压器衬套的介电损耗和变压器的接地电流磁芯。讨论了系统中包含的每个单元的理论,进一步讨论了该系统的现场数据和通过现场测试的非现场数据进行比较。在其长时间稳定运行期间,该监控系统已成功地在变压器内部发生的高温过热故障,气体超大气体与传统光谱分析的结果一致。最后,真正的核心 - 环聊测试的结果支持了该系统的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号