Several distribution-class extruded-cables subjected to laboratory-accelerated aging were examined for partial discharges (PD). The cables were subjected to different load cycling while fully immersed in water to obtain different aging conditions. PD initiated in these cables was measured at rated and at elevated voltages. Correlation between the PD-signature and the insulation-defects type was examined. This was achieved by comparing the PD frequency, magnitude and phase angles of different insulation defects. Correlation between the PD level and AC breakdown voltage of these cables also is presented in this paper. The same investigations also were repeated on several cables removed from service after 15-20 years of service. Correlation between the PD levels and the cable remaining life also was investigated.
机译:检查了几种经过实验室加速老化的配电级挤压电缆的局部放电(PD)。电缆在完全浸入水中的同时经受了不同的负载循环,从而获得了不同的老化条件。在额定电压和升高的电压下测量了这些电缆中引发的PD。检查了PD签名和绝缘缺陷类型之间的相关性。这是通过比较不同绝缘缺陷的PD频率,幅度和相角来实现的。本文还介绍了这些电缆的PD电平与AC击穿电压之间的关系。在15-20年的服役后退役的几根电缆也进行了同样的调查。还研究了PD水平与电缆剩余寿命之间的相关性。